Home Savings CalculatorHome Savings Calculator

BTU Calculator

Work out how much heat a room needs in BTU and watts, and the radiator size to buy for a boiler or a heat pump.

Your Inputs

L
W
H
°C

Heat Needed

Live
Heat loss on a cold day
3,749 BTU
1,099 W · 1.10 kW21°C inside, -3°C outside
Where the heat goesWattsBTU
External walls162553
Windows3021,032
Ceiling00
Floor235803
Ventilation3991,362
Radiator size1,099 WΔT50 rating · boiler
BTU per m²26814.0 m² floor
Room volume33.6 m³1.5 air changes an hour
Temperature lift24°Cinside minus outside
Walls, windows, floor & ceiling 700 W (64%)Ventilation 399 W

About this estimate

  • Fabric and ventilation heat loss method
  • Typical U-values for UK wall, window and loft types
  • Radiator output shown at the ΔT50 catalogue rating
  • Shows where the heat is lost
  • No personal data required

Estimate only. Real heat loss depends on exact construction, draughts, location and exposure — use a professional heat loss survey to design a heating system.

How the heat loss is worked out

  • Each surface loses U-value × area × temperature difference
  • Ventilation loses 0.33 × air changes × room volume × temperature difference
  • Room type sets the inside temperature and air changes
  • Watts × 3.412 = BTU per hour
  • Radiator size is converted to its ΔT50 catalogue rating

This is the steady heat loss on a cold day, with typical U-values for each construction. An installer’s room-by-room survey uses your exact walls, location and exposure, and is what a heat pump should be designed from.

How to work out the BTU a room needs

A room needs enough heat to replace what it loses on a cold day. That heat escapes two ways: through the walls, windows, floor and ceiling, and with the air that leaks out and is replaced by cold air from outside. This BTU calculator adds up both, then gives the answer in BTU per hour and in watts, plus the radiator size to buy.

Heat lost through surfaces

Each surface loses U-value × area × temperature difference, in watts. The U-value says how easily heat passes through: about 2.1 for an uninsulated solid brick wall, 0.5 for an insulated cavity wall, and 2.8 for older double glazing.

Heat lost with the air

Ventilation loss = 0.33 × air changes per hour × room volume × temperature difference. A living room is taken as changing its air 1.5 times an hour and a bathroom 3 times, which is why bathrooms need more heat than their size suggests.

Watts to BTU

Multiply watts by 3.412 to get BTU per hour. A 1,000W radiator gives out 3,412 BTU/hr. UK radiator catalogues list both, but manufacturers rate the output at ΔT50, which matters a lot for heat pumps.

Worked example: a 4m × 3.5m living room

Two external walls, insulated cavity, older double glazing, ground floor, heated room above. 21°C inside, −3°C outside.

Where the heat goesWattsShare
External walls162 W15%
Windows302 W27%
Floor235 W21%
Ventilation399 W36%
Total1,099 W (3,749 BTU)100%

That is about 268 BTU per m² of floor. The ceiling loses nothing here because there is a heated room above.

Why insulation changes the answer so much

The same living room, changing only the walls or windows.

ConstructionHeat lossBTU per hour
New build walls, modern glazing876 W2,990
Insulated cavity, older double glazing1,099 W3,749
Insulated cavity, single glazing1,315 W4,486
Unfilled cavity, older double glazing1,423 W4,854
Solid brick, older double glazing1,617 W5,518

Filling the cavity cuts this room’s heat loss by 324W on a cold day. That is why rule-of-thumb BTU figures based only on room size are so often wrong.

Radiator sizes for boilers and heat pumps

What ΔT50 means

Radiator output depends on how much hotter the water is than the room. Catalogues quote it at ΔT50 — roughly 70°C water in a 20°C room, which suits a traditional boiler. Run cooler water and the same radiator gives out much less.

Sizing for a heat pump

At ΔT30 a radiator gives about 51% of its rated output, and at ΔT20 about 30%. So the example living room needs a 1,099W radiator with a boiler, about 2,135W of rated output at ΔT30, and about 3,616W at ΔT20. Choose Heat pump above to see the size for your room.

Compare the running costs with the heating cost calculator, and read heat pump vs boiler for why flow temperature matters.

Bedrooms, bathrooms and kitchens

Bedrooms

Bedrooms are designed to 18°C and change their air more slowly. A 3.5m × 3m bedroom with one external wall and an insulated loft above needs about 430W, or 1,469 BTU — far less than the living room.

Bathrooms

Bathrooms are kept at 22°C with fast air changes for moisture. A 2.5m × 2m bathroom with one external wall needs about 424W (1,446 BTU) — almost the same as a bedroom twice its size. Most of that is ventilation, which is why a towel rail alone often leaves a bathroom cool.

Kitchens

Kitchens are designed to 18°C because cooking and appliances add heat, but extractor fans raise the air change rate. Choose Kitchen as the room type and the calculator applies both.

Getting a reliable figure

Inputs that matter most

  • Wall type — solid, unfilled cavity or insulated
  • Window size and glazing age
  • Whether the space above or below is heated
  • The outside design temperature for where you live

When to get a survey

This is a good guide for choosing a radiator. For a whole new heating system, especially a heat pump, installers carry out a room-by-room heat loss calculation using your exact construction and location. Before that, improving insulation lowers every room’s figure — see cutting an energy bill for where it sits in the order of savings.

Frequently asked questions